DocumentCode :
1442939
Title :
Generator loading limits for impulse testing low-inductance windings
Author :
Kannan, S.R. ; Narayana Rao, Y.
Author_Institution :
Indian Institute of Technology, Department of Electrical Engineering, Madras, India
Volume :
122
Issue :
5
fYear :
1975
fDate :
5/1/1975 12:00:00 AM
Firstpage :
535
Lastpage :
538
Abstract :
The performance of the conventional resistance-front-control (r.f.c.) impulse generator, the inductance-frontcontrol (i.f.c.) generator and the modified resistance-front-control (m.r.f.c.) generator, during testing of lowvoltage, low-inductance windings, have been analysed. Expressions have been developed, which enable prediction of the generator parameters for the production of standard lightning impulse waves. These are then extended to find the respective loading limits, beyond which a standard wave cannot be produced. The loading range, over which each type of generator is best utilised, has been ascertained.
Keywords :
impulse testing; pulse generators; transformer testing; generator loading limits; generator parameters; impulse generator; impulse testing; low inductance windings; production of standard lightning impulse waves;
fLanguage :
English
Journal_Title :
Electrical Engineers, Proceedings of the Institution of
Publisher :
iet
ISSN :
0020-3270
Type :
jour
DOI :
10.1049/piee.1975.0146
Filename :
5253489
Link To Document :
بازگشت