DocumentCode :
1444079
Title :
An Islanding Detection Method for a Grid-Connected System Based on the Goertzel Algorithm
Author :
Kim, Jae-Hyung ; Kim, Jun-Gu ; Ji, Young-Hyok ; Jung, Yong-Chae ; Won, Chung-Yuen
Author_Institution :
Sch. of Inf. & Commun. Eng., Sungkyunkwan Univ., Suwon, South Korea
Volume :
26
Issue :
4
fYear :
2011
fDate :
4/1/2011 12:00:00 AM
Firstpage :
1049
Lastpage :
1055
Abstract :
Islanding refers to a condition of a distributed generator (DG) in that it continues to power a location even though power from the grid is no longer present. This condition can be dangerous to grid workers who may not realize that the load is still powered even though there is no power from the grid. Adverse effects of islanding are low power quality, grid-protection interference, equipment damage, and personnel safety hazards. For these reasons, DG systems must detect an islanding condition and immediately stop producing power; this is referred to as anti-islanding. Islanding detection methods can be categorized into two major approaches: the passive and active methods. The passive methods are based on measurement of the natural effects of islanding. The active methods use intentional transients or harmonic effects. When the power generated by the DG matches the load power consumption, passive methods fail due to the small natural effects of islanding. Therefore, the passive methods have a nondetection zone (NDZ). The active methods can reduce the NDZ size. However, these methods reduce the grid power quality. In this paper, a novel anti-islanding method (AIM) is proposed. A single-phase DG using the proposed AIM injects the output current with a little harmonic current into the grid and monitors the harmonic components of the voltage at the point of common coupling using the Goertzel algorithm. The Goertzel algorithm is a kind of discrete Fourier transform. It extracts the magnitude and phase of the desired frequency from the input signal, with a minimum computation. The proposed islanding detection algorithm resolves the NDZ but also the bad effects on the grid power quality due to injecting harmonic components qualified by the interconnection standard. The proposed islanding detection method was verified using PSIM (see www.powersimtech.com) simulations and experimental results.
Keywords :
discrete Fourier transforms; distributed power generation; power consumption; power supply quality; DFT; Goertzel algorithm; active methods; anti-islanding method; discrete Fourier transform; equipment damage; grid-connected system; grid-protection interference; harmonic components; intentional transients; interconnection standard; islanding detection method; load power consumption; low power quality; nondetection zone; passive methods; personnel safety hazards; single-phase distributed generator; Discrete Fourier transforms; Harmonic analysis; Impedance; Inverters; Monitoring; Power harmonic filters; Power quality; Discrete Fourier transform; Goertzel; distributed generator; harmonic; islanding; nondetection zone;
fLanguage :
English
Journal_Title :
Power Electronics, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8993
Type :
jour
DOI :
10.1109/TPEL.2011.2107751
Filename :
5709991
Link To Document :
بازگشت