The effects of mutual induction between parallel transmission lines on current flow to ground faults
Author :
Holbeck, John I. ; Lantz, Martin J.
Author_Institution :
Bonneville Power Administration, Portland, Oreg.
Volume :
62
Issue :
11
fYear :
1943
Firstpage :
712
Lastpage :
715
Abstract :
THIS paper is intended to present some of the problems encountered in determining unbalanced fault currents and unusual results that may be expected on systems with parallel lines on a common right of way. Correct results are required so that proper co-ordination and application of relays may be accomplished. Fault studies must be made and constantly revised, as a power system changes and expansions take place. Also, future conditions must be studied so that intelligent selection may be made of circuit breakers and current transformers. It is the purpose of this paper to discuss
Keywords :
Circuit faults; Conductors; Equivalent circuits; Impedance; Induction motors; Power transmission lines; Relays;