Abstract :
Measurements of coupling factors between ground wires and phase conductors, as a function of ground-wire voltage, have been made for a sufficient number of cases to determine them for any of the standard transmission-line configurations. It was found that the effect of corona can be expressed in terms of an effective corona ground-wire radius to be used in the conventional coupling-factor equations. Curves are also presented for the quick determination of coupling factors for all standard line configurations. A photographic study of the visual characteristics of surge corona was made for a comparison with the effective radius and with 60-cycle corona. Actual measurements were made for potentials up to about 2,000 kv, but the data were extrapolated to 6,000 kv with what is considered to be reasonably good accuracy.