DocumentCode :
1444386
Title :
The effect of corona on coupling factors between ground wires and phase conductors
Author :
Mccann, G. D.
Author_Institution :
Westinghouse Electric and Manufacturing Company, East Pittsburgh, Pa.
Volume :
62
Issue :
12
fYear :
1943
Firstpage :
818
Lastpage :
826
Abstract :
Measurements of coupling factors between ground wires and phase conductors, as a function of ground-wire voltage, have been made for a sufficient number of cases to determine them for any of the standard transmission-line configurations. It was found that the effect of corona can be expressed in terms of an effective corona ground-wire radius to be used in the conventional coupling-factor equations. Curves are also presented for the quick determination of coupling factors for all standard line configurations. A photographic study of the visual characteristics of surge corona was made for a comparison with the effective radius and with 60-cycle corona. Actual measurements were made for potentials up to about 2,000 kv, but the data were extrapolated to 6,000 kv with what is considered to be reasonably good accuracy.
Keywords :
Companies; Conductors; Corona; Couplings; Substations; Voltage measurement; Wires;
fLanguage :
English
Journal_Title :
Electrical Engineering
Publisher :
ieee
ISSN :
0095-9197
Type :
jour
DOI :
10.1109/EE.1943.6436055
Filename :
6436055
Link To Document :
بازگشت