• DocumentCode
    1444522
  • Title

    Sparkover in the rod-plane gap under combined direct and impulse voltages

  • Author

    Allen, N.L. ; Huang, C.F. ; Cornick, K.J. ; Greaves, D.A.

  • Author_Institution
    Dept. of Electr. Eng. & Electron., Univ. of Manchester Inst. of Sci. & Technol., UK
  • Volume
    145
  • Issue
    5
  • fYear
    1998
  • fDate
    9/1/1998 12:00:00 AM
  • Firstpage
    207
  • Lastpage
    214
  • Abstract
    Experiments are described in which composite voltages, produced by superimposing positive and negative switching impulse voltages on pre-stressing positive or negative direct voltages, are applied to a rod-plane gap of lengths up to 1 m. Changes in 50% sparkover voltages are described over a range of positive and negative pre-stressing voltages; it is shown that negative pre-stressing always reduces the composite sparkover voltage, but that positive pre-stress increases the positive composite sparkover voltage and reduces the negative one. Recordings of photomultiplier observations and `still´ photography of pre-breakdown corona have been made at the 50% sparkover level and the results related to the sparkover characteristics. It is shown that the latter depend on the way in which leader initiation is affected by the preceding DC corona
  • Keywords
    air gaps; high-voltage engineering; overvoltage protection; power system protection; power system transients; HV engineering; combined direct/impulse voltages; composite voltages; leader initiation; negative pre-stressing; photomultiplier observations; positive pre-stress; preceding DC corona; rod-plane gap; sparkover; still photography;
  • fLanguage
    English
  • Journal_Title
    Science, Measurement and Technology, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2344
  • Type

    jour

  • DOI
    10.1049/ip-smt:19982208
  • Filename
    729709