DocumentCode
1444522
Title
Sparkover in the rod-plane gap under combined direct and impulse voltages
Author
Allen, N.L. ; Huang, C.F. ; Cornick, K.J. ; Greaves, D.A.
Author_Institution
Dept. of Electr. Eng. & Electron., Univ. of Manchester Inst. of Sci. & Technol., UK
Volume
145
Issue
5
fYear
1998
fDate
9/1/1998 12:00:00 AM
Firstpage
207
Lastpage
214
Abstract
Experiments are described in which composite voltages, produced by superimposing positive and negative switching impulse voltages on pre-stressing positive or negative direct voltages, are applied to a rod-plane gap of lengths up to 1 m. Changes in 50% sparkover voltages are described over a range of positive and negative pre-stressing voltages; it is shown that negative pre-stressing always reduces the composite sparkover voltage, but that positive pre-stress increases the positive composite sparkover voltage and reduces the negative one. Recordings of photomultiplier observations and `still´ photography of pre-breakdown corona have been made at the 50% sparkover level and the results related to the sparkover characteristics. It is shown that the latter depend on the way in which leader initiation is affected by the preceding DC corona
Keywords
air gaps; high-voltage engineering; overvoltage protection; power system protection; power system transients; HV engineering; combined direct/impulse voltages; composite voltages; leader initiation; negative pre-stressing; photomultiplier observations; positive pre-stress; preceding DC corona; rod-plane gap; sparkover; still photography;
fLanguage
English
Journal_Title
Science, Measurement and Technology, IEE Proceedings -
Publisher
iet
ISSN
1350-2344
Type
jour
DOI
10.1049/ip-smt:19982208