DocumentCode
1444613
Title
Calculation of transient due to fault initiation on a double-circuit transmission line
Author
Balasubramanian, R. ; Gupta, S.
Author_Institution
Indian Institute of Technology, Department of Electrical Engineering, Kanpur, India
Volume
123
Issue
6
fYear
1976
fDate
6/1/1976 12:00:00 AM
Firstpage
537
Lastpage
542
Abstract
In this paper, a mathematical analysis of a transient due to initiation of a single line-earth fault at any intermediate point on a double-circuit transmission line, using the modified Fourier-transform method, is presented. The double-circuit line has been modelled, taking into account the mutual coupling between the two circuits. A typical 400kV double-circuit line is considered and the fault transient is evaluated for both transposed and untransposed configurations of the line. The effect of the frequency dependence of line parameters on the fault transient has been investigated.
Keywords
fault currents; power transmission lines; transients; Fourier transform; double circuit transmission; fault initiation; frequency dependence of line parameters; mathematical analysis; single line earth fault; transient;
fLanguage
English
Journal_Title
Electrical Engineers, Proceedings of the Institution of
Publisher
iet
ISSN
0020-3270
Type
jour
DOI
10.1049/piee.1976.0121