• DocumentCode
    1445158
  • Title

    Characteristic Comparison of the Superconducting Fault Current Limiter With Various Bypass Reactors

  • Author

    Chang, Ki Sung ; Park, Dong Keun ; Yang, Seong Eun ; Kim, Young Jae ; Chu, Sung Yul ; Ahn, Min Cheol ; Ko, Tae Kuk

  • Author_Institution
    Sch. of Electr. & Electr. Eng., Yonsei Univ., Seoul, South Korea
  • Volume
    20
  • Issue
    3
  • fYear
    2010
  • fDate
    6/1/2010 12:00:00 AM
  • Firstpage
    1190
  • Lastpage
    1193
  • Abstract
    A resistive superconducting fault current limiter (SFCL) has two drawbacks-relatively higher impedance and longer recovery time than the requirement of the electric power system. A parallel-connected bypass reactor (BPR) can be a solution to both problems. As a stage of proof-of-concept, an SFCL comprised of an YBCO S/N switch and a Bi2223-BPR had been presented in the former paper. Although the previous one has shorter recovery time, the generated impedance after a fault was too low to satisfy the requirement of the power system. To apply the SFCL into the power system, the SFCL has proper impedance during the fault. Therefore, we proposed bypass reactors to achieve higher impedance than the previous one in this paper. The SFCLs with a bypass reactor were fabricated and short-circuit test with the SFCLs were conducted. The test results were compared in point of current limiting characteristics and recovery. This research would be applied to a conceptual design of BPR.
  • Keywords
    fault current limiters; reactors (electric); Bi2223-BPR; YBCO S/N switch; bypass reactors; electric power system; recovery time; resistive superconducting fault current limiter; short-circuit test; Bypass reactor; SFCL; YBCO;
  • fLanguage
    English
  • Journal_Title
    Applied Superconductivity, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1051-8223
  • Type

    jour

  • DOI
    10.1109/TASC.2010.2040920
  • Filename
    5433263