    Distance protection performance during simultaneous faults

  • Author

    Cook, V.

  • Author_Institution
    University College, Electrical Engineering Department, Cardiff, UK
  • Volume
    124
  • Issue
    2
  • fYear
    1977
  • fDate
    2/1/1977 12:00:00 AM
  • Firstpage
    141
  • Lastpage
    146
  • Abstract
    The paper considers the performance of both unswitched and switched distance protection schemes using polarised-mho relays on systems subjected to simultaneous faults. The disturbances considered are flashoverfaults to earth, cross-country earth faults and open-conductor plus earth faults on a double-circuit 132 kV transmission system. Consideration is also given to protection performance for double earth faults separatedby a star-delta transformer. Differences in protection philosophies of British and Continental relay manufacturers are highlighted and a comparison is given for switched schemes employing overcurrent starter units.
  • Keywords
    fault currents; overcurrent protection; power system protection; relay protection; transmission networks; distance protection; disturbances; double circuit 132 kV transmission system; earth faults; flashover; overcurrent; protection performance; relay; simultaneous faults; switched schemes; unswitched schemes;