DocumentCode :
1446754
Title :
Abnormal currents in distribution transformers due to lightning
Author :
Bryant, J. M. ; Newman, Mike
Author_Institution :
University of Minnesota, Minneapolis, Minn.
Volume :
61
Issue :
8
fYear :
1942
Firstpage :
564
Lastpage :
568
Abstract :
Abnormal currents in distribution transformers due to lightning are analyzed both theoretically and from field experiences. Under certain conditions of direct stroke transferred through the arrester to the neutral of the secondary winding, excessive currents may wreck the secondary windings by electromagnetic forces. Long-duration surges, or shorter repeated surges, saturate the transformer cores producing greatly increased surge currents in the primary windings which influence fuse failures. The saturation of the cores by unidirectional lightning surges also brings about increased power-frequency magnetizing currents influencing sectionalizing-fuse and circuit-breaker operations.
Keywords :
Circuit faults; Fuses; Lightning; Surge protection; Surges; Transformer cores; Windings;
fLanguage :
English
Journal_Title :
Electrical Engineering
Publisher :
ieee
ISSN :
0095-9197
Type :
jour
DOI :
10.1109/EE.1942.6436471
Filename :
6436471
Link To Document :
بازگشت