Abstract :
This paper presents a discussion and analysis of short circuits for low-voltage distribution systems. Many distribution systems are supplied from transformers connected in delta on the low-voltage side with the mid-tap of one secondary winding, or with one corner of the delta, connected to ground. As a result, short circuits on these systems often involve failure to ground, and an accurate analysis for these faults is of value. An original analysis of power-leg-to-ground and light-leg-to-ground short circuits is presented together with formulas for line-to-line and three-phase faults. A study of short circuits on the secondary circuits of single-phase transformers supplied from three-phase systems is also included, thereby giving a comprehensive treatment of distribution short circuits. The paper also includes a discussion of the effects of resistance in limiting short-circuit currents and the voltage rise of the secondary neutral above ground potential caused by transformer failure and resistance to ground.