Title :
Development and Deployment of Saturated-Core Fault Current Limiters in Distribution and Transmission Substations
Author :
Moriconi, Franco ; De La Rosa, Francisco ; Darmann, Frank ; Nelson, Albert ; Masur, Larry
Author_Institution :
Zenergy Power Inc., Burlingame, CA, USA
fDate :
6/1/2011 12:00:00 AM
Abstract :
Zenergy Power has been developing an inductive-type of fault current limiter (FCL) for electric power grid applications. The FCL employs a magnetically saturating reactor concept which acts as a variable inductor in an electric circuit. In March 2009 Zenergy Power, with funding from the California Energy Commission and the U.S. Department of Energy (DOE), installed an FCL in the Avanti distribution circuit of Southern California Edison´s Shandin substation in San Bernardino, CA. Rated at 15 kV and 1,250 amperes steady-state, the “Avanti” device is the first superconductor FCL installed in a US utility. In January 2010, the “Avanti” device successfully limited its first series of real-world faults when the circuit experienced multiple single-phase and three-phase faults. After successfully validating the performance of a new “compact” saturated-core FCL, Zenergy Power received contracts to install a 12 kV, 1,250 amperes compact FCL in the CE Electric UK grid in early 2011 and a 138 kV, 1,300 amperes FCL at the Tidd substation of American Electric Power in late 2011.
Keywords :
distribution networks; inductive power transmission; power grids; substations; superconducting fault current limiters; American Electric Power; Avanti device; Avanti distribution circuit; CE Electric UK grid; California Energy Commission; San Bernardino; Southern California Edison´s Shandin substation; Tidd substation; U.S. Department of Energy; Zenergy Power; current 1250 A; current 1300 A; distribution substations; electric circuit; electric power grid; inductive-type fault current limiter; magnetically saturating reactor; saturated-core fault current limiters; superconductor FCL; transmission substations; variable inductor; voltage 12 kV; voltage 138 kV; Circuit faults; Coils; Fault currents; High temperature superconductors; Inductors; Magnetic cores; Testing; Fault current limiters (FCLs); high-temperature superconductors; saturable cores; short circuit currents; superconducting magnets;
Journal_Title :
Applied Superconductivity, IEEE Transactions on
DOI :
10.1109/TASC.2011.2104932