• DocumentCode
    145127
  • Title

    The optimization of 750kV anti-ice-flashing composite insulator string

  • Author

    Nan Jing ; Xu Tao ; Wan Xiaodong ; Yao Tao ; Xu Zuoming ; Li Xuelin ; Liu Qin

  • Author_Institution
    China Electr. Power Res. Inst., Wuhan, China
  • Volume
    1
  • fYear
    2014
  • fDate
    26-28 April 2014
  • Firstpage
    205
  • Lastpage
    209
  • Abstract
    Composite insulators have been widely used for its excellent flashover endurance capability, but the umbrella of standard composite insulators are easily been bridged in icing condition. Flashover problems caused by icing insulator have a serious threat to the safe operation of transmission lines,. It is the key technologies for the safe operation of power system which should be solved as soon as possible. The influence of two types of composite insulator umbrella structure (common type and anti-ice type) on iced AC flashover voltage characteristics in the same structure length, as well as same artificial pollution and artificial icing test conditions, but also the method of artificial iced flashover test on composite insulator were introduced. Iced flashover test results showed that the ice bridge formation could be prevented or extended if the umbrella structure design of anti-ice-type composite insulators was more reasonable. For the 750kV composite insulator under the same conditions of artificial pollution test (SDD/NSDD=0.08/0.48mg/cm2) and artificial icing test (when icing water converted to 20 °C, the conductivity is 100μS/cm and the iced thickness from 15mm), it is shown that AC iced flashover voltage of Anti-ice type increased 12%~28% than common type. Upon the existent theoretical and experimental results and based on a great of laboratory investigations carried out in environment laboratory of China UHV AC test base, for the first time this paper studies systematically the insulators shed optimization which will contribute to the designation for Ultra-UHV anti-icing composite insulators.
  • Keywords
    composite insulators; flashover; ice; insulator contamination; insulator testing; power transmission lines; China UHV AC test base; anti-ice-flashing composite insulator string optimization; artificial iced flashover test method; artificial icing test conditions; artificial pollution test; composite insulator umbrella structure; flashover endurance capability; ice bridge formation; iced AC flashover voltage characteristics; power system safe operation; size 15 mm; structure length; temperature 20 degC; transmission lines; ultra-UHV anti-icing composite insulators; voltage 750 kV; Bridge circuits; Flashover; Ice; Insulators; Pollution; Power transmission lines; anti-icing; composite insulator; flashover characteristic; umbrella optimization;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Information Science, Electronics and Electrical Engineering (ISEEE), 2014 International Conference on
  • Conference_Location
    Sapporo
  • Print_ISBN
    978-1-4799-3196-5
  • Type

    conf

  • DOI
    10.1109/InfoSEEE.2014.6948098
  • Filename
    6948098