• DocumentCode
    1453077
  • Title

    Dielectric strength of double and single-break vacuum interrupters: experiments with real HV demonstration bottles

  • Author

    Giere, S. ; Karner, H.C. ; Knobloch, H.

  • Author_Institution
    Tech. Univ. Braunschweig, Germany
  • Volume
    8
  • Issue
    1
  • fYear
    2001
  • fDate
    3/1/2001 12:00:00 AM
  • Firstpage
    43
  • Lastpage
    47
  • Abstract
    This paper describes dielectric experiments on vacuum interrupters for HV applications. The investigations were performed with two different vacuum bottle designs. The difference between these objects is the number of breaker units per bottle and slight deviations in the shielding arrangement. On this basis the dielectric results of one and two interrupter units in one housing are discussed. The experiments show the gain of dielectric strength caused by conditioning effects, and were carried out under ac and lightning impulse voltage (LIV)
  • Keywords
    electric strength; impulse testing; shielding; switchgear testing; vacuum interrupters; HV demonstration bottles; ac impulse voltage; conditioning effects; dielectric strength; double-break vacuum interrupters; lightning impulse; shielding arrangement; single-break vacuum interrupters; Circuit testing; Dielectric breakdown; Dielectrics and electrical insulation; Gases; Interrupters; Power transformer insulation; Sulfur hexafluoride; Switchgear; Vacuum technology; Voltage;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/94.910424
  • Filename
    910424