• DocumentCode
    1455461
  • Title

    Relation of traveling waves to fault locators

  • Author

    Lewis, L. J.

  • Author_Institution
    University of Washington, Seattle, Wash.
  • Volume
    71
  • Issue
    1
  • fYear
    1952
  • Firstpage
    58
  • Lastpage
    58
  • Abstract
    THE RESPONSE of a fault locator utilizing traveling waves to measure distance to a fault depends not only on the design of the fault locator but also on the characteristics of the waves themselves. A mathematical analysis of a 3-phase system shows that because of losses and coupling between lines, two surge components are produced which travel at different speeds. The slow wave is equivalent to a current flow in the three wires in parallel, with a ground return; the fast wave is equivalent to current flow confined to the line conductors.
  • Keywords
    Conductors; Couplings; Equations; Generators; Mathematical model; Reflection; Surges;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1952.6437895
  • Filename
    6437895