A comparison of power measuring systems
Author :
Simonson, Pär ; Svensson, Stefan ; Rydler, Karl-Erik
Author_Institution :
Swedish Nat. Tseting & Res. Inst., Boras, Sweden
Volume :
46
Issue :
2
fYear :
1997
fDate :
4/1/1997 12:00:00 AM
Firstpage :
423
Lastpage :
425
Abstract :
An automatic zero-power-factor standard has been designed and compared with a digital sampling wattmeter standard. The agreement of the two power measuring standards at 120 V, 5 A, and zero power factor is within a few μW/VA. The paper describes the standards, the phase errors and uncertainties of the two standards
Keywords :
measurement errors; measurement standards; power factor; power measurement; wattmeters; 120 V; 5 A; automatic zero-power-factor standard; digital sampling wattmeter standard; measuring standards; phase errors; power measuring systems; uncertainties; Automatic testing; Current measurement; Electrical resistance measurement; Measurement standards; Phase measurement; Power measurement; Reactive power; Sampling methods; Shunt (electrical); Wattmeters;