DocumentCode :
1455912
Title :
A low-current multistage clamp-on current transformer with ratio errors below 50×10-6
Author :
So, Eddy ; Bennett, David A.
Author_Institution :
Inst. for Nat. Meas. Stand., Nat. Res. Council of Canada, Ottawa, Ont., Canada
Volume :
46
Issue :
2
fYear :
1997
fDate :
4/1/1997 12:00:00 AM
Firstpage :
454
Lastpage :
458
Abstract :
An electronically aided multistage technique is applied to a hand-held openable-core damp-on current transformer which enables accurate low current measurements to be made over a wide dynamic and frequency range of operation, for use in conjunction with highly accurate active/reactive power and energy meters, and harmonic power analyzers. The clamp on current transformer can be used to measure currents in the range from 1 A to 200 A, at frequencies between 50 Hz ad 5 kHz, with ratio errors of less than 50×10-6 in both magnitude and phase
Keywords :
current transformers; electric current measurement; measurement errors; power meters; 1 to 200 A; 50 Hz to 5 kHz; active power; dynamic range; frequency range; harmonic power analyzers; low current measurements; multistage clamp-on current transformer; openable-core damp-on current transformer; ratio errors; reactive power; Clamps; Current measurement; Current transformers; Dynamic range; Frequency measurement; Harmonic analysis; Phase measurement; Power system harmonics; Reactive power; Watthour meters;
fLanguage :
English
Journal_Title :
Instrumentation and Measurement, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9456
Type :
jour
DOI :
10.1109/19.571883
Filename :
571883
Link To Document :
بازگشت