• DocumentCode
    1456104
  • Title

    Regulation of a 115-megawatt turbogenerator

  • Author

    Cornelius, H. A. ; Cawson, W. F. ; Cory, H. W.

  • Author_Institution
    Public Service Company of Northern Illinois, Chicago, Ill.
  • Volume
    71
  • Issue
    3
  • fYear
    1952
  • fDate
    3/1/1952 12:00:00 AM
  • Firstpage
    221
  • Lastpage
    221
  • Abstract
    A 115-MEGAWATT 95-per-cent power-factor generator, having a short-circuit ratio of 0.66, has lost synchronism occasionally during faults in the 20 years it has been in service at the Waukegan Station of the Public Service Company of Northern Illinois. During faults the the generator terminal voltage became so low that the generator lost a large share of its load and the rotor accelerated, thus allowing the generator to swing out of synchronism. It was decided to investigate possibilities of using automatic voltage regulation to maintain generator voltage.
  • Keywords
    Automatic voltage control; Circuit faults; Generators; Regulators; Transient analysis; Turbogenerators;