DocumentCode
1456545
Title
Leak location in fluid filled cables using the PFT method
Author
Ghafurian, Reza ; Dietz, Russell N. ; Rodenbaugh, Thomas ; Dominguez, Jason ; Tai, Noah
Author_Institution
Consolidated Edison Co., New York, NY, USA
Volume
14
Issue
1
fYear
1999
fDate
1/1/1999 12:00:00 AM
Firstpage
18
Lastpage
22
Abstract
A new method of pinpointing dielectric fluid leaks on pipe-type and self-contained power cables using perfluorocarbon tracer (PFT) is presented. The method has successfully been used on the Con Edison transmission system to locate leaks of dielectric fluid on both types of cables. Application of the PFT technique does not require feeder deenergization and provides major advantages over the conventional method of freeze and pressure testing. Description of the method and results of field application are presented in the paper
Keywords
insulation testing; leak detection; power cable insulation; power cable testing; dielectric fluid; dielectric fluid leak detection; feeder deenergization; fluid-filled power cables; perfluorocarbon tracer; pipe-type power cable; self-contained power cable; Atmospheric modeling; Cable insulation; Conductors; Dielectrics and electrical insulation; Leak detection; Power & Energy Society; Power system reliability; Printing; Steel; Testing;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.736673
Filename
736673
Link To Document