DocumentCode :
146040
Title :
Load blinding stabilisation for DOC relays subjected to reverse load flow
Author :
Wixon, A. ; Venkataraman, K. ; Newman, Paul ; Maleka, K.
Author_Institution :
Alstom Grid Substation Autom. Solutions, Stafford, UK
fYear :
2014
fDate :
March 31 2014-April 3 2014
Firstpage :
1
Lastpage :
9
Abstract :
Evolution of modern power systems have seen an increase in the generation at the distribution end of the system, thus bringing to an end the uni-directional power flow of traditional systems. Reverse load flow from distribution to transmission is now becoming more common, which is problematic for the DOC protection which could mal-operate if the exported load exceeds the current threshold. This paper discusses the use of load blinders to prevent mal-operation of the DOC relay during export conditions, whilst maintaining maximum sensitivity for resistive faults on the sub-transmission network.
Keywords :
load flow; overcurrent protection; power system stability; power transmission faults; power transmission protection; relay protection; DOC relay protection; directional overcurrent protection; load blinding stabilisation; mal-operation prevent; power distribution system; power generation system; power transmission system; resistive fault; reverse load flow; subtransmission network; unidirectional power flow;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection (DPSP 2014), 12th IET International Conference on
Conference_Location :
Copenhagen
Print_ISBN :
978-1-84919-834-9
Type :
conf
DOI :
10.1049/cp.2014.0077
Filename :
6822885