    Decreasing momentary outages with specific distribution feeder improvements

  • Author

    Coate, Brian D. ; Wareham, Don C.

  • Author_Institution
    Tipmont REMC, Linden, IN, USA
  • Volume
    37
  • Issue
    2
  • fYear
    2001
  • Firstpage
    458
  • Lastpage
    463
  • Abstract
    This paper presents a cost-effective method of reducing momentary interruptions. Two main concepts are discussed. The first is targeting selected zones with increased maintenance to improve overall reliability of the entire feeder, and the second is overcurrent coordination for trip saving on the substation feeder circuit breaker. Trip saving is the intentional coordination of tap fuses off main feeders so that a fault on the tap will not cause a fast operation of the main breaker. Other topics discussed are the resetting of instantaneous tripping of the substation breaker, use of tap reclosers, and increasing lightning/animal protection on key parts of the feeder
  • Keywords
    lightning protection; maintenance engineering; power distribution faults; power distribution protection; power distribution reliability; animal protection; distribution feeder improvements; feeder reliability; lightning protection; maintenance; momentary outages reduction; substation breaker; tap fuse coordination; tap reclosers; Animals; Circuit breakers; Circuit faults; Fuses; Lightning; Maintenance; Power system transients; Protective relaying; Reliability engineering; Substation protection;