DocumentCode
146106
Title
A new and fast method of determining the faulted circuit in the parallel lines with use of one-end current measurements
Author
Saha, M.M. ; Balcerek, P. ; Pierz, P. ; Rosolowski, E. ; Izykowski, J.
Author_Institution
ABB AB, Vasteras, Sweden
fYear
2014
fDate
March 31 2014-April 3 2014
Firstpage
1
Lastpage
6
Abstract
This paper presents a new, very fast method for selection of faulted circuit in parallel lines for both uncompensated and series-compensated lines. It suits for protection of parallel uncompensated or series-compensated lines and uses one-end phase currents measurements only. The developed algorithm has been tested and evaluated using signals taken from ATPEMTP versatile simulations. A detailed model of considered transmission line including the SCs&MOVs banks as well as the measurement channels has been developed. Using this model, the reliable fault data on a double-circuit uncompensated/series-compensated transmission line as well as for faults outside the line have been generated under variety of fault conditions. The sample results of this evaluation are presented and discussed.
Keywords
EMTP; capacitors; electric current measurement; fault currents; fault location; power transmission faults; power transmission lines; power transmission protection; varistors; ATP-EMTP versatile simulation; MOV; SC; double circuit series compensated transmission line; double circuit uncompensated transmission line; fault circuit determination; measurement channel; metal oxide varistor; one end phase current measurement; parallel lines; series capacitors; distance protection; double-circuit line; fault detection; faulted circuit discrimination; series compensation;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection (DPSP 2014), 12th IET International Conference on
Conference_Location
Copenhagen
Print_ISBN
978-1-84919-834-9
Type
conf
DOI
10.1049/cp.2014.0110
Filename
6822918