Title :
Influence of distributed generation on the protection principles of a 70 kV/15 kV transformer in antenna: The zero-sequence overvoltage protection U0>
Author :
Debrue, F. ; Gonzalez, Christopher ; Wijnhoven, Thomas ; Goossens, P. ; Driesen, Johan
Author_Institution :
KU Leuven, Leuven, Belgium
fDate :
March 31 2014-April 3 2014
Abstract :
Distributed Generation (DG) influences the traditional protection schemes. In this paper the influence of DG on the protections of the Belgian grid operator, Elia, is explained for a 70 kV/15 kV transformer in antenna. Based on the method of the symmetrical components, the detection of two different types of protections, zero-sequence overvoltage, U0>, and negative-sequence overvoltage, U2>, are analysed in case of a line-to-ground fault, a broken conductor without earth fault and a broken conductor with earth fault at the transformer side. The U0>relay is to be installed in the star point at the primary side of the transformer and measures the zero-sequence voltage. The U2>relay calculates the negative-sequence voltage at the secondary side of the transformer.
Keywords :
antennas; distributed power generation; earthing; power generation faults; power generation protection; power transformer protection; Belgian grid operator; Elia; antenna; broken conductor; distributed generation; earth fault; electric power systems; line-to-ground fault; negative-sequence overvoltage protection principle; symmetrical components; transformer; voltage 15 kV; voltage 70 kV; zero-sequence overvoltage protection principle; zero-sequence voltage measurement; Power system protection; distributed generation;
Conference_Titel :
Developments in Power System Protection (DPSP 2014), 12th IET International Conference on
Conference_Location :
Copenhagen
Print_ISBN :
978-1-84919-834-9
DOI :
10.1049/cp.2014.0124