DocumentCode :
1461511
Title :
Investigation of single unit flashovers in HVDC insulator strings
Author :
Ishikawa, Kouichi ; Kageyama, Hiroshi ; Yamada, Yasuhiro ; Matsuoka, Ryosuke ; Ito, Susumu ; Sakanishi, Kenji
Author_Institution :
Kansai Electr. Power Co. Inc., Osaka, Japan
Volume :
11
Issue :
4
fYear :
1996
fDate :
10/1/1996 12:00:00 AM
Firstpage :
1888
Lastpage :
1894
Abstract :
In HVDC transmission lines, a special phenomenon, so-called single unit flashover, is observed under some special conditions. Only one or two insulator units repeat flashovers, not resulting in an overall flashover along the string. However, higher magnitudes of audible noise, radio and television interferences may give a serious problem. Based on an investigation on ±500 kV full scale insulator strings, the higher occurrence probability of single unit flashovers under cold-wet-switch-on conditions was clarified compared with normal continuous operating voltage conditions. The effectiveness of the authors´ newly proposed countermeasures to prevent single unit flashovers was demonstrated by experiments in laboratory and in the field
Keywords :
HVDC power transmission; flashover; insulator testing; power transmission lines; 500 kV; HVDC insulator strings; HVDC transmission lines; audible noise; cold-wet-switch-on conditions; continuous operating voltage conditions; countermeasures; field tests; laboratory tests; radio interference; single unit flashover; television interference; Acoustic noise; Dielectrics and electrical insulation; Flashover; HVDC transmission; Indium tin oxide; Leakage current; Power transmission lines; Surface resistance; TV interference; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.544272