    Sequential tripping of steam turbine generators: Working Group report

  • Author

    Fennell, Everett ; Kozminski, Kevin ; Bajpai, Munnu ; Easterday-McPadden, Steve ; Elmore, Walt ; Fromen, Charles ; Gardell, Jon ; Hartmann, Wayne ; Hurley, Joe ; Kerrigan, Patrick ; Khunkhun, Kumul ; Mozina, Charles J. ; Nail, George ; Patel, Subhash ; Pe

  • Author_Institution
    ABB Power P&D Co., North Brunswick, NJ, USA
  • Volume
    34
  • Issue
    6
  • fYear
    1998
  • Firstpage
    1411
  • Lastpage
    1418
  • Abstract
    The practice of tripping generator breakers immediately following a boiler/turbine trip exposes a steam turbine-generator to a potentially damaging overspeed operating condition. This paper describes the use of the sequential trip mode as a means of minimizing the exposure to possible unit damage following a boiler/turbine trip. Included is a comparison of the application of devices used by several major steam turbine-generator manufacturers in accomplishing sequential tripping of the unit. This paper also discusses the differences in the devices used in implementing the tripping scheme and those applied as backup motoring protection. Additionally, the paper provides guidance in the selection of which functions should and should not be used to initiate sequential tripping
  • Keywords
    circuit breakers; machine protection; steam power stations; steam turbines; turbogenerators; backup motoring protection; overspeed operating condition; selection guidelines; sequential circuit breaker tripping; steam power plants; steam turbine-generator protection; Boilers; Manufacturing; Nails; Power & Energy Society; Power generation; Power system protection; Switches; Temperature; Turbines; Valves;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/28.739029
  • Filename
    739029