DocumentCode
1461787
Title
Sequential tripping of steam turbine generators: Working Group report
Author
Fennell, Everett ; Kozminski, Kevin ; Bajpai, Munnu ; Easterday-McPadden, Steve ; Elmore, Walt ; Fromen, Charles ; Gardell, Jon ; Hartmann, Wayne ; Hurley, Joe ; Kerrigan, Patrick ; Khunkhun, Kumul ; Mozina, Charles J. ; Nail, George ; Patel, Subhash ; Pe
Author_Institution
ABB Power P&D Co., North Brunswick, NJ, USA
Volume
34
Issue
6
fYear
1998
Firstpage
1411
Lastpage
1418
Abstract
The practice of tripping generator breakers immediately following a boiler/turbine trip exposes a steam turbine-generator to a potentially damaging overspeed operating condition. This paper describes the use of the sequential trip mode as a means of minimizing the exposure to possible unit damage following a boiler/turbine trip. Included is a comparison of the application of devices used by several major steam turbine-generator manufacturers in accomplishing sequential tripping of the unit. This paper also discusses the differences in the devices used in implementing the tripping scheme and those applied as backup motoring protection. Additionally, the paper provides guidance in the selection of which functions should and should not be used to initiate sequential tripping
Keywords
circuit breakers; machine protection; steam power stations; steam turbines; turbogenerators; backup motoring protection; overspeed operating condition; selection guidelines; sequential circuit breaker tripping; steam power plants; steam turbine-generator protection; Boilers; Manufacturing; Nails; Power & Energy Society; Power generation; Power system protection; Switches; Temperature; Turbines; Valves;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.739029
Filename
739029
Link To Document