DocumentCode :
1461819
Title :
An area substation load model in the presence of harmonics
Author :
Mancini, R. ; Zabar, Z. ; Birenbaum, L. ; Levi, E. ; Hajagos, J. ; Kalinowsky, S.
Author_Institution :
Polytechnic Univ., Brooklyn, NY, USA
Volume :
11
Issue :
4
fYear :
1996
fDate :
10/1/1996 12:00:00 AM
Firstpage :
2013
Lastpage :
2019
Abstract :
A computer program is described which simulates the effects of harmonics introduced at the distribution level (13.8 kV/120 or 277 V) by nonlinear loads and which can be integrated into existing load flow codes. Each device is represented by a table of harmonics (amplitude and phase) of the current when energized by a sinusoidal voltage. For simplicity, it is assumed that the current waveform remains unchanged when the applied voltage becomes “slightly” distorted by the harmonic components of the current. An estimate is made of the error caused by this assumption
Keywords :
digital simulation; distribution networks; load (electric); power system analysis computing; power system harmonics; substations; 120 V; 13.8 kV; 277 V; area substation load model; current waveform; distribution level; harmonic components; harmonics; load flow codes; nonlinear loads; sinusoidal voltage; Capacitors; Harmonic distortion; Load modeling; Power system harmonics; Power transformer insulation; Samarium; Substations; Switched-mode power supply; Variable speed drives; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.544289
Filename :
544289
Link To Document :