DocumentCode
1462660
Title
Circulating Ground Currents
Author
Brown, William A. ; Kennedy, James M. ; Linkhart, Charles
Author_Institution
Schneider Electr., Nashville, TN, USA
Volume
17
Issue
3
fYear
2011
Firstpage
56
Lastpage
65
Abstract
THe paralleling of uninterruptible power supplies (UPSs) with generators during UPS bypass operations can result in high magnitude circulating ground currents under certain conditions. This article explores the phenomena that cause this system behavior, presents data from an actual documented occurrence, and discusses the methods to reduce or eliminate such circulating currents.
Keywords
electric generators; uninterruptible power supplies; UPS; generators; high magnitude circulating ground currents; uninterruptible power supplies; Circuit breakers; Current measurement; Generators; Harmonic analysis; Switches; Uninterruptible power systems; Windings;
fLanguage
English
Journal_Title
Industry Applications Magazine, IEEE
Publisher
ieee
ISSN
1077-2618
Type
jour
DOI
10.1109/MIAS.2010.939637
Filename
5722083