DocumentCode :
1466427
Title :
The determination of FFA concentration in transformer oil by fluorescence measurements
Author :
Blue, R. ; Uttamchandani, D. ; Farish, O.
Author_Institution :
Div. of Optoelectron., Strathclyde Univ., Glasgow, UK
Volume :
5
Issue :
6
fYear :
1998
fDate :
12/1/1998 12:00:00 AM
Firstpage :
892
Lastpage :
895
Abstract :
Condition monitoring of the paper winding of power transformers involves the measurement of the concentration of 2-furaldehyde, also called furfuraldehyde (FFA) in the transformer oil. Measuring the concentration of FFA in the oil gives a reliable indication of the condition of the paper insulation. This measurement has routinely been performed by using techniques such as high performance liquid chromatography. We report for the first time the use of fluorescence-based methods for the assessment of FFA in transformer oil
Keywords :
condition monitoring; fluorescence; insulation testing; organic compounds; paper; power transformer insulation; spectrochemical analysis; transformer oil; transformer windings; 2-furaldehyde; FFA concentration; condition monitoring; fluorescence measurement; furfuraldehyde; paper insulation; power transformer; transformer oil; winding; Condition monitoring; Fluorescence; Instruments; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Solid state circuits; Spectroscopy; Thermal degradation;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/94.740772