Title :
A Novel Fuzzy-Logic Approach for Furan Estimation in Transformer Oil
Author :
Abu-Siada, A. ; Lai, Sin P. ; Islam, Syed M.
Author_Institution :
Dept. of Electr. & Comput. Eng., Curtin Univ., Perth, WA, Australia
fDate :
4/1/2012 12:00:00 AM
Abstract :
An ultraviolet-to-visible (UV-Vis) spectroscopic analysis based on the fuzzy-logic approach has been developed for furan content measurement in transformer oil. Following the successful identification and quantification of furan derivatives in transformer oil by the ASTM D 5837 standard, the new approach is able to approximate the furan content with a more convenient and economical method. Since the furan concentration level would determine the absorption intensity in the UV-Vis spectral range, the fuzzy-logic software model developed would exploit this characteristic to aggregate the furans content level in transformer oil. The UV-Vis spectral response sensitivity to ambient temperature was also studied. The proposed technique provide a convenient alternative to conventional techniques, namely: high-performance liquid chromatography (HPLC) or gas chromatography-mass spectrometry (GC/MS) methods.
Keywords :
approximation theory; fuzzy logic; power engineering computing; power transformer insulation; spectral analysis; transformer oil; ultraviolet spectra; visible spectra; ASTM D 5837 standard; furan content approximation; furan content measurement; furan derivative identification; furan derivative quantification; fuzzy logic software model; gas chromatography; high performance liquid chromatography; mass spectrometry; spectral response sensitivity; transformer oil; ultraviolet to visible spectroscopy; Absorption; Aging; Bandwidth; Oil insulation; Power transformer insulation; Spectroscopy; Furfurals; fuzzy logic; transformer insulation oil; ultraviolet to visible spectroscopy;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2012.2186986