Passive shunt harmonic filters for low and medium voltage: a cost comparison study
Author :
Kawann, Cornelia ; Emanuel, Alexander E.
Author_Institution :
Graz Univ. of Technol., Austria
Volume :
11
Issue :
4
fYear :
1996
fDate :
11/1/1996 12:00:00 AM
Firstpage :
1825
Lastpage :
1831
Abstract :
This paper presents the cost of 480 V and 13.8 kV passive shunt harmonic filters tuned at 300, 420, 660 and 780 Hz. The cost is presented in function of the kVA of the load served by the filters, the 60 Hz reactive power produced by the filter end the total non60 Hz apparent power of the load. The main conclusion of this work is that for nonlinear loads in excess of 1 MVA it is more economical to use filter centers connected on the 13.8 kV side
Keywords :
costing; economics; harmonic distortion; load (electric); passive filters; power filters; power system harmonics; 13.8 kV; 300 Hz; 420 Hz; 480 V; 60 Hz; 660 Hz; 780 Hz; LV; MV; cost comparison; load apparent power; nonlinear loads; passive shunt harmonic filters; power systems; reactive power production; Active filters; Costs; Harmonic filters; Medium voltage; Power engineering and energy; Power filters; Power generation economics; Power harmonic filters; Power system harmonics; Reactive power;