    The functions of ground preference in carrier-current relay schemes

  • Volume
    63
  • Issue
    6
  • fYear
    1944
  • fDate
    6/1/1944 12:00:00 AM
  • Firstpage
    437
  • Lastpage
    437
  • Abstract
    A. R. van C. Warrington (General Electric Company, Philadelphia, Pa.): In addition to the ground preference troubles cited by the authors, an external ground fault has to be cleared before a simultaneous internal fault can be cleared. Furthermore, spurious residual current caused by current-transformer inaccuracy during a heavy internal phase fault can delay or prevent tripping.