DocumentCode
1473482
Title
Icing flashover characteristics and discharge process of 500 kV AC transmission line suspension insulator strings
Author
Liu, Yunpeng ; Gao, Song ; Huang, Daochun ; Yao, Tao ; WU, Xiong ; Hu, Yi ; Cai, Wei
Author_Institution
Dept. of Electr. Eng., North China Electr. Power Univ., Baoding, China
Volume
17
Issue
2
fYear
2010
fDate
4/1/2010 12:00:00 AM
Firstpage
434
Lastpage
442
Abstract
The icing flashover characteristics and discharge processes of 500 kV ac transmission line long insulator strings energized in the ice accretion were studied. The influence of pollution and grading rings (including simulated conductor) on heavy ice-covered insulators¿ flashover voltage were considered in this paper. Based on the artificial icing test results, it was found that 1) under the severe icing conditions and three salt deposit density (SDD) levels of PSDD=0.1, 0.05, 0.025 mg/cm2, compared with 500 kV transmission line rated phase to ground voltage, the flashover voltages of 28 units XWP2-160 porcelain double-shed insulator are 20.5% lower, 13.1% lower and 2.3% higher respectively; and the values of the FXBW4-500/160 composite insulator are 18.7% lower, 12.0% lower and 4.3% higher respectively. 2) equipped with the given grading ring and simulated conductor the icing flashover stress of 28 units XWP2-160 is lower than those without grading ring and simulated conductor under the three pollution degrees. The discharge process of the icing flashover and relevant factors were investigated also, which shows that 1) the locations of the air gaps on icing insulators are not completely random. 2) arcs on long insulator strings require more time to reach a critical length, hence, the arc propagation might be easily influenced by the decreasing of melted water conductivity and ice shedding than short insulator strings.
Keywords
air gaps; composite insulators; flashover; ice; power transmission lines; air gaps; composite insulator; discharge process; ice accretion; icing flashover characteristics; pollution; salt deposit density; suspension insulator strings; transmission lines; voltage 500 kV; Conductors; Flashover; Ice; Insulation; Insulator testing; Pollution; Porcelain; Stress; Transmission lines; Voltage; Air gap, 500 kV transmission line, flashover voltage, grading ring, icing melting, pollution, SDD, water conductivity.;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2010.5448098
Filename
5448098
Link To Document