• DocumentCode
    1473514
  • Title

    Application of identification methods for predicting the flashover voltage of contaminated insulators covered with ice

  • Author

    Sabri, Y. ; Farzaneh, M. ; Zhang, J.

  • Author_Institution
    Canada Res. on Atmos. Icing Eng. of Power Network (INGIVRE), Univ. du Quebec a Chicoutimi, Chicoutimi, QC, Canada
  • Volume
    17
  • Issue
    2
  • fYear
    2010
  • fDate
    4/1/2010 12:00:00 AM
  • Firstpage
    451
  • Lastpage
    457
  • Abstract
    The arc characteristics on contaminated insulator surfaces covered with ice were investigated. The arc constants (A, n), as well as the ac re-ignition parameters (K, b) were determined using a simplified cylindrical physical model. Based on identification methods, a new approach for calculating the residual voltage is introduced. These results will serve to extend the previous mathematical model developed at CIGELE for its application to predicting the flashover voltage of contaminated insulators covered with ice. The model was successfully applied to a five-unit IEEE standard insulator string, and the calculated results were in good agreement with the experiments.
  • Keywords
    flashover; insulator contamination; CIGELE; IEEE standard insulator string; ac re-ignition parameters; contaminated insulator surfaces; flashover voltage; identification methods; simplified cylindrical physical model; Dielectrics and electrical insulation; Environmentally friendly manufacturing techniques; Flashover; Ice surface; Mathematical model; Pollution; Power system modeling; Road transportation; Surface contamination; Voltage; Outdoor insulation, flashover phenomenon, electrical arc, identification methods, contaminated insulators covered with ice, flashover modeling.;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2010.5448100
  • Filename
    5448100