• DocumentCode
    1475176
  • Title

    The next step in interrupting capacity — 5,000,000 kva

  • Author

    Hill, A. W. ; Leeds, W. M.

  • Author_Institution
    Westinghouse Electric and Manufacturing Company, East Pittsburgh, Pa.
  • Volume
    64
  • Issue
    6
  • fYear
    1945
  • fDate
    6/1/1945 12:00:00 AM
  • Firstpage
    317
  • Lastpage
    323
  • Abstract
    Serious consideration is being given to large power-system interconnections which could develop short circuits at certain locations in excess of 3,500,000 kva. High-voltage oil-circuit-breaker capabilities for such heavy duty are reviewed in this paper, the fundamental design requirements outlined, and results of high-power laboratory tests presented which demonstrate that interrupting capacity ratings as high as 5,000,000 kva are feasible. Laboratory test methods for demonstrating these extremely high arc rupturing ratings are evaluated. The importance of verifying high-speed reclosing performance with high-power tests is emphasised, and on the basis of data already obtained, standard reclosing time intervals considerably less than 20 cycles are foreseen.
  • Keywords
    Circuit breakers; Circuit faults; Companies; Interrupters; Laboratories; Standards;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1945.6441065
  • Filename
    6441065