• DocumentCode
    1478496
  • Title

    Linear couplers, field tests and experience at York and Middletown, Pa.

  • Author

    Harder, E. L. ; Klemmer, E. H. ; Neidig, R. E.

  • Author_Institution
    Westinghouse Electric Corporation, East Pittsburgh, Pa.
  • Volume
    65
  • Issue
    3
  • fYear
    1946
  • fDate
    3/1/1946 12:00:00 AM
  • Firstpage
    107
  • Lastpage
    113
  • Abstract
    THE system of bus protection using linear couplers, or air-core mutual reactors, in place of current transformers was described before the Institute in January 1942.1 By special design the mutual reactors were made astatic or insensitive to outside fields. Through the use of air core the troublesome problem of saturation of iron by the d-c transient component of short-circuit current was eliminated. At the same time adequate energy was derived for decisive relay operation. The coupler secondaries were connected in a series loop including the relay to form a bus protective system.
  • Keywords
    Circuit breakers; Circuit faults; Couplers; Current transformers; Fault currents; Relays; Stress;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1946.6441602
  • Filename
    6441602