DocumentCode
1478496
Title
Linear couplers, field tests and experience at York and Middletown, Pa.
Author
Harder, E. L. ; Klemmer, E. H. ; Neidig, R. E.
Author_Institution
Westinghouse Electric Corporation, East Pittsburgh, Pa.
Volume
65
Issue
3
fYear
1946
fDate
3/1/1946 12:00:00 AM
Firstpage
107
Lastpage
113
Abstract
THE system of bus protection using linear couplers, or air-core mutual reactors, in place of current transformers was described before the Institute in January 1942.1 By special design the mutual reactors were made astatic or insensitive to outside fields. Through the use of air core the troublesome problem of saturation of iron by the d-c transient component of short-circuit current was eliminated. At the same time adequate energy was derived for decisive relay operation. The coupler secondaries were connected in a series loop including the relay to form a bus protective system.
Keywords
Circuit breakers; Circuit faults; Couplers; Current transformers; Fault currents; Relays; Stress;
fLanguage
English