DocumentCode
1478782
Title
Expose hidden failures to prevent cascading outages [in power systems]
Author
Phadke, A.G. ; Thorp, J.S.
Author_Institution
Virginia Polytech. Inst. & State Univ., Blacksburg, VA, USA
Volume
9
Issue
3
fYear
1996
fDate
7/1/1996 12:00:00 AM
Firstpage
20
Lastpage
23
Abstract
Major blackouts are rare events, but their impact can be catastrophic. A study of significant disturbances reported by NERC in the period from 1984 through 1988 indicates that protective relays are involved in one way or another in 75 percent of major disturbances. A common scenario is that the relay has an undetected (hidden) defect that was exposed due to the conditions created by other disturbances. For example, nearby faults, overloads, or reverse power flows expose the defective relay and cause a false trip, which exacerbates the situation. Given the importance of hidden failure modes in traditional relaying systems, intervention by computer-based rational control schemes is proposed in this article. Relays with high-vulnerability indices can be identified, and their vulnerable functions and failure modes identified. Countermeasures to reduce or eliminate the likelihood of the hidden failure of key relays can be provided
Keywords
electrical faults; failure analysis; power system protection; power system relaying; power system reliability; relay protection; cascading outages prevention; faults; hidden failure modes; major disturbances; overloads; power supply reliability; power systems; protective relays; reverse power flows; vulnerability; Condition monitoring; Councils; Digital relays; Failure analysis; Lighting control; Power system analysis computing; Power system faults; Power system protection; Power system relaying; Protective relaying;
fLanguage
English
Journal_Title
Computer Applications in Power, IEEE
Publisher
ieee
ISSN
0895-0156
Type
jour
DOI
10.1109/67.526849
Filename
526849
Link To Document