DocumentCode
1479632
Title
Apparent power transducer for three-phase three-wire system
Author
Kusui, S. ; Kogane, M.
Author_Institution
Nippon Inst. of Technol., Saitama, Japan
Volume
35
Issue
1
fYear
1999
fDate
1/7/1999 12:00:00 AM
Firstpage
5
Lastpage
7
Abstract
In a newly developed transducer apparent power is measured by using a multiplier, in which the AC component of the output is used. For a three-phase three-wire system, two multipliers are used according to the so-called `two wattmeter´ method. The AC output components are +30° and -30° phase-shifted, respectively, and then the difference is converted to a DC signal which corresponds to the total apparent power
Keywords
power measurement; apparent power transducer; multiplier; three-phase three-wire system; two wattmeter method;
fLanguage
English
Journal_Title