DocumentCode
1479743
Title
A new electronic timing relay for reducing outages on power circuits
Author
Dlouhy, Frank S.
Author_Institution
Oklahoma Gas and Electric Company, Oklahoma City, Okla.
Volume
65
Issue
7
fYear
1946
fDate
7/1/1946 12:00:00 AM
Firstpage
407
Lastpage
411
Abstract
This paper describes a new timing relay for controlling relaying time on automatically reclosed circuit breakers on which inverse-time overcurrent relays are supplemented by instantaneous overcurrent relays. This device incorporates the advantages of instantaneous circuit breaker opening on the first, and in some cases the second, tripout to clear transient faults, and inverse-time opening on subsequent tripouts to obtain co-ordination with branch or sectionalizing fuses. It was designed for universal application on feeder circuits of the Oklahoma Gas and Electric Company system. Certain features which provide for optimum service reliability were incorporated in the design.
Keywords
Cathodes; Circuit breakers; Circuit faults; Contacts; Relays; Switches; Timing;
fLanguage
English
Journal_Title
Electrical Engineering
Publisher
ieee
ISSN
0095-9197
Type
jour
DOI
10.1109/EE.1946.6441807
Filename
6441807
Link To Document