DocumentCode
1479826
Title
Magnetic field and electromagnetic force analysis of 3-phase air-core superconducting power transformer
Author
Yamaguchi, Hiroshi ; Kataoka, Teruo ; Matsuoka, Hiroki ; Mouri, Tomohide ; Nishikata, Shoji ; Sato, Yukihiko
Author_Institution
Frontier Technol. Div., Electrotech. Lab., Tsukuba, Japan
Volume
11
Issue
1
fYear
2001
fDate
3/1/2001 12:00:00 AM
Firstpage
1490
Lastpage
1493
Abstract
The superconducting windings of the air-core superconducting power transformer have possibilities of being exposed to a higher magnetic field than those of the iron-core transformer because of no special paths for magnetic flux. Thus, in this paper, the magnetic field and electromagnetic force acting on the windings of an experimental 3-phase air-core superconducting transformer are analyzed. From the results, it has become clear that the superconducting windings of the air-core transformer are exposed to a 3-dimensional magnetic field containing a rotational component
Keywords
electromagnetic forces; magnetic fields; magnetic flux; power transformers; superconducting transformers; transformer windings; 3-dimensional magnetic field; 3-phase air-core superconducting power transformer; 3-phase air-core superconducting transformer; electromagnetic force; electromagnetic force analysis; magnetic field; magnetic flux; rotational component; superconducting windings; Electromagnetic analysis; Electromagnetic forces; Magnetic analysis; Magnetic fields; Magnetic flux; Power transformers; Superconducting cables; Superconducting coils; Superconducting transmission lines; Windings;
fLanguage
English
Journal_Title
Applied Superconductivity, IEEE Transactions on
Publisher
ieee
ISSN
1051-8223
Type
jour
DOI
10.1109/77.920057
Filename
920057
Link To Document