DocumentCode
1481158
Title
DC reactor effect on bridge type superconducting fault current limiter during load increasing
Author
Hoshino, Tsutomu ; Salim, Khosru-Mohammad ; Nishikawa, Massanori ; Muta, Itsuya ; Nakamura, Taketsune
Author_Institution
Graduate Sch. of Eng., Kyoto Univ., Japan
Volume
11
Issue
1
fYear
2001
fDate
3/1/2001 12:00:00 AM
Firstpage
1944
Lastpage
1947
Abstract
In high power applications, the fault current limiter has been discussed for many years because of some limitations of conventional circuit breakers. Many types of fault current limiter have already been introduced in papers. In this work, a simple bridge-type fault current limiter has been designed and constructed. The performances of the limiter have been tested successfully. In the bridge-type current limiter, a DC reactor appears in the line when the connected load is increasing. This causes a voltage drop across the load terminal during load changing. The DC reactor effect of the current limiter has been studied. Some experimental results regarding the reactor effect of the limiter have been considered and compared with the results obtained from computer simulation
Keywords
bridge circuits; fault current limiters; load (electric); power system protection; superconducting devices; DC reactor effect; bridge-type superconducting fault current limiter; computer simulation; load changing; load increase; load terminal; voltage drop; Bridge circuits; Circuit breakers; Circuit testing; Computer simulation; Current limiters; Fault current limiters; Fault currents; Inductors; Performance evaluation; Voltage;
fLanguage
English
Journal_Title
Applied Superconductivity, IEEE Transactions on
Publisher
ieee
ISSN
1051-8223
Type
jour
DOI
10.1109/77.920232
Filename
920232
Link To Document