• DocumentCode
    1481158
  • Title

    DC reactor effect on bridge type superconducting fault current limiter during load increasing

  • Author

    Hoshino, Tsutomu ; Salim, Khosru-Mohammad ; Nishikawa, Massanori ; Muta, Itsuya ; Nakamura, Taketsune

  • Author_Institution
    Graduate Sch. of Eng., Kyoto Univ., Japan
  • Volume
    11
  • Issue
    1
  • fYear
    2001
  • fDate
    3/1/2001 12:00:00 AM
  • Firstpage
    1944
  • Lastpage
    1947
  • Abstract
    In high power applications, the fault current limiter has been discussed for many years because of some limitations of conventional circuit breakers. Many types of fault current limiter have already been introduced in papers. In this work, a simple bridge-type fault current limiter has been designed and constructed. The performances of the limiter have been tested successfully. In the bridge-type current limiter, a DC reactor appears in the line when the connected load is increasing. This causes a voltage drop across the load terminal during load changing. The DC reactor effect of the current limiter has been studied. Some experimental results regarding the reactor effect of the limiter have been considered and compared with the results obtained from computer simulation
  • Keywords
    bridge circuits; fault current limiters; load (electric); power system protection; superconducting devices; DC reactor effect; bridge-type superconducting fault current limiter; computer simulation; load changing; load increase; load terminal; voltage drop; Bridge circuits; Circuit breakers; Circuit testing; Computer simulation; Current limiters; Fault current limiters; Fault currents; Inductors; Performance evaluation; Voltage;
  • fLanguage
    English
  • Journal_Title
    Applied Superconductivity, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1051-8223
  • Type

    jour

  • DOI
    10.1109/77.920232
  • Filename
    920232