Title :
Reduced transformer insulation
Author :
Hunter, E. M. ; Meador, J. R. ; Rudge, W. J.
Author_Institution :
General Electric Company, Pittsfield, Mass.
fDate :
6/1/1957 12:00:00 AM
Abstract :
THE DEVELOPMENT of the Thyrite (registered trade mark) Magne-Valve station-type lightning arrester with its improved lightning protective characteristics made it possible to reduce power transformer BIL by two insulation classes under certain conditions. This was the culmination of a 5-year program which had three objectives: (1) to obtain service experience with the new arresters used with high-voltage two-step-down transformers; (2) to get additional information on switching surges occurring in service, and their effect on strength of transformer insulation; and (3) to study the long-time steady-state strength of transformer insulation.
Keywords :
Oil insulation; Power transformer insulation; Surge protection; Surges; Switches;
Journal_Title :
Electrical Engineering
DOI :
10.1109/EE.1957.6442571