DocumentCode :
1484254
Title :
Effect of geomagnetically induced current on the loss of transformer tank
Author :
Zhang, Boming ; Liu, L. ; Liu, Yanbing ; McVey, M. ; Gardner, R. Matthew
Author_Institution :
North China Electr. Power Univ., Beijing, China
Volume :
4
Issue :
5
fYear :
2010
fDate :
5/1/2010 12:00:00 AM
Firstpage :
373
Lastpage :
379
Abstract :
Geomagnetically induced current (GIC) can cause half-cycle saturation of transformer. The saturation can increase the stray flux entering into transformer tank, so the tank loss will increase. This study presents a two-dimensional finite element (2D FE) transformer model and the losses of tank wall, tank top and tank bottom are computed, respectively. Based on the 2D FE magnetic field, the factors that influence the tank loss of transformer with GIC are discussed. The influences of magnetic shunt, transformer types, step-up transformer or step-down transformer, and transformer power factor on the tank loss are analysed in detail. As a consequence, the transformer types and transformer power factor have large influence on the increase of tank loss caused by GIC.
Keywords :
finite element analysis; geomagnetism; power factor; power transformers; 2D FE magnetic field; 2D finite element transformer model; geomagnetically induced current; half-cycle saturation; magnetic shunt; tank loss; transformer power factor; transformer tank;
fLanguage :
English
Journal_Title :
Electric Power Applications, IET
Publisher :
iet
ISSN :
1751-8660
Type :
jour
DOI :
10.1049/iet-epa.2009.0192
Filename :
5458296
Link To Document :
بازگشت