DocumentCode
1485273
Title
Determination of interface flow margin using the modified continuation power flow in voltage stability analysis
Author
Song, H. ; Kim, S. ; Lee, B. ; Kwon, S.-H. ; Ajjarapu, V.
Author_Institution
Sch. of Electr. Eng., Korea Univ., Seoul, South Korea
Volume
148
Issue
2
fYear
2001
fDate
3/1/2001 12:00:00 AM
Firstpage
128
Lastpage
132
Abstract
A new concept of interface flow margin in terms of steady-state voltage stability is introduced. The interface flow margin is the active power flow margin of the key transmission lines between one region and others under a fixed load demand condition. In addition, a technique is proposed to trace interface flow-voltage (f-V) curves by applying a continuation method. From the f-V curves, the interface flow margin can be easily obtained, which is useful to determine the secure flow limit of the specified interface. In the case study, an illustrative example with the New England 39-bus system is shown
Keywords
load flow; power system analysis computing; power system dynamic stability; power system security; power transmission lines; transmission network calculations; computer simulation; interface flow margin; interface flow margin determination; interface flow-voltage curves; modified continuation power flow; secure flow limit; transmission lines; voltage stability analysis;