Field Test and Simulation of a 400-kV Cross-Bonded Cable System
Author
Gudmundsdottir, Unnur Stella ; Gustavsen, Bjørn ; Bak, Claus Leth ; Wiechowski, Wojciech
Author_Institution
Energinet.dk, Fredericia, Denmark
Volume
26
Issue
3
fYear
2011
fDate
7/1/2011 12:00:00 AM
Firstpage
1403
Lastpage
1410
Abstract
This paper discusses cable modeling for long high-voltage ac underground cables. In investigating the possibility of using long cables instead of overhead lines, the simulation results must be trustworthy. Therefore, model validation is of great importance. This paper gives a benchmark case for measurements on a 400-kV cable system with cross-bonded sheaths. This paper describes in detail the modeling procedure for the cable system and compares simulation results with the transient field test results. It is shown that although the main characteristics of the waveforms are well reproduced in the initial transient, there are significant deviations between the simulation and measurement results. An analysis indicates that the main cause for the deviation is inadequate representation of the current distribution on conductors since the modeling approach does not take proximity effects into account. The measurement results can be received by contacting the first author of this paper.
Keywords
cable sheathing; power cable testing; underground cables; cable modeling; cross-bonded cable system; cross-bonded sheaths; field simulation; field test; high- voltage AC underground cables; overhead lines; transient field test results; voltage 400 kV; Bonding; Cable shielding; Conductors; Current measurement; Grounding; Power cables; Voltage measurement; Insulated cables; model accuracy; modeling; power system transients; proximity effect; simulation;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2010.2084600
Filename
5743045
Link To Document