• DocumentCode
    1490634
  • Title

    Electrical and Thermal Analyses of Parallel Single-Conductor Cable Installations

  • Author

    Du, Patrick Y. ; Wang, X.H.

  • Author_Institution
    Dept. of Building Services Eng., Hong Kong Polytech. Univ., Kowloon, China
  • Volume
    46
  • Issue
    4
  • fYear
    2010
  • Firstpage
    1534
  • Lastpage
    1540
  • Abstract
    The unequal current distribution in parallel single-conductor cable installations can lead to an excessive temperature rise. This paper presents a cable model and a procedure of coupled electrical and thermal analyses for the evaluation of the current, loss, and temperature in the cables of concern. The cable model and analytical method were tested experimentally on a cable system in the laboratory. The procedure was applied to evaluate the current rating and the temperature rise in a particular single-conductor installation. It is concluded that the parallel cable installation without proper cable rephrasing derates the cables significantly. The third-order harmonic current can cause a significant reduction of the current rating if its distortion is over 30%.
  • Keywords
    conductors (electric); current distribution; harmonic distortion; power cables; thermal analysis; coupled electrical-thermal analyses; current distribution; distortion reduction; electrical-thermal analyses; parallel single-conductor cable installations; third-order harmonic current; Cable; current distribution; loss; temperature;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2010.2049819
  • Filename