Abstract :
Sandia frequency shift (SFS) falls under the active islanding detection methods that rely on frequency drift to detect an islanding condition for inverter-based distributed generation. Active islanding detection methods are commonly tested on constant RLC loads where the load´s active power is directly proportional to the square of voltage and is independent on the system frequency. Since the SFS method relies primarily on frequency to detect islanding, the load´s active power frequency dependence could have an impact on its performance and the nondetection zone (NDZ). In this paper, the impact of the load´s active power frequency dependence on the performance of the SFS method, during an islanding condition, is analyzed. A NDZ model that takes into account the load´s frequency dependence parameter is derived mathematically and validated through digital simulation. The results show that the load´s frequency dependence has a significant impact on the NDZ of the SFS method and thus is an important factor to consider when designing and testing this method.
Keywords :
RLC circuits; digital simulation; distributed power generation; invertors; load (electric); NDZ model; RLC loads; SFS islanding detection method; Sandia frequency shift; active islanding detection methods; digital simulation; inverter-based distributed generation; load active power frequency dependence; nondetection zone; Current measurement; Distortion measurement; Distributed control; Frequency dependence; Inverters; Performance analysis; Permission; Power system protection; System testing; Voltage; Distributed generation (DG); Sandia frequency shift (SFS); inverter; islanding detection;
Journal_Title :
Industrial Electronics, IEEE Transactions on
DOI :
10.1109/TIE.2009.2033482