Design and evaluation of a wind farm protection relay
Author
Haslam, S.J. ; Crossley, P.A. ; Jenkins, N.
Author_Institution
Centre for Electr. Energy, Univ. of Manchester Inst. of Sci. & Technol., UK
Volume
146
Issue
1
fYear
1999
fDate
1/1/1999 12:00:00 AM
Firstpage
37
Lastpage
44
Abstract
The paper describes the design and evaluation of a protection relay for wind farms with fixed-speed induction generators. The relay provides short-circuit protection for a medium-voltage collection circuit and the medium-voltage (MV) and low-voltage (LV) windings of the generator-transformers connected to it. The ability to protect the generator-transformers allows a significant reduction in wind farm construction cost, since the MV fuses normally used to protect the generator-transformers are not required. The authors discuss how the operating characteristic for the protection was designed, implemented in a processor-based relay and then tested using a wind farm simulator and test set. A selection of test results are to illustrate how the relay performs occur on the protected collection LV terminals of a generator-transformers or on the utility network. The paper also discusses how the relay performed when installed at the Cemmaes wind farm in Wales for a 12 month site trial
Keywords
asynchronous generators; machine protection; overcurrent protection; power system protection; power system relaying; power transformer protection; relay protection; short-circuit currents; transformer windings; wind power plants; fixed-speed induction generators; generator-transformer windings; medium-voltage collection circuit; operating characteristic; short-circuit protection; wind farm protection relay;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings-
Publisher
iet
ISSN
1350-2360
Type
jour
DOI
10.1049/ip-gtd:19990045
Filename
756481
Link To Document