DocumentCode :
1496120
Title :
Analysis of transformer inrush transients in offshore electrical systems
Author :
Smith, K.S. ; Ran, L. ; Leyman, B.
Author_Institution :
Dept. of Comput. & Electr. Eng., Heriot-Watt Univ., Edinburgh, UK
Volume :
146
Issue :
1
fYear :
1999
fDate :
1/1/1999 12:00:00 AM
Firstpage :
89
Lastpage :
95
Abstract :
Large transformers are electrically close to generators in an offshore power system. Energising such transformers causes significant inrush currents, which are sustained for several seconds. The voltage dip on the generator bus then initiates a response from the automatic voltage regulator (AVR). Using a numerical simulation, the lightly damped response of the AVR is shown to modify the inrush transient. Other on-line transformers can be sent into magnetic saturation. Site measurements confirm the features of the transient predicted by the simulation. The paper shows that a detailed model is required if the inrush current on an isolated offshore power system is to be correctly predicted
Keywords :
natural gas technology; oil technology; power system control; power system transients; power transformers; transient analysis; voltage regulators; AVR; automatic voltage regulator; generator bus voltage dip; inrush transient modification; lightly damped response; magnetic saturation; offshore electrical systems; transformer energisation; transformer inrush transients analysis;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:19990056
Filename :
756488
Link To Document :
بازگشت