Title :
Aging of dry-type transformer insulation
Author :
Stewart, H. C. ; Whitman, L. C.
Author_Institution :
General Electric Company, Pittsfield, Mass.
fDate :
5/1/1949 12:00:00 AM
Abstract :
THERE IS a fundamental difference in the life of insulation containing organic material operated in an insulating liquid as contrasted to the same insulation operated in a gas medium. When operated in an insulating liquid, the liquid tends to replace the material deteriorated and so maintains electrical strength. When operated at a high temperature in a gas medium, as the deterioration progresses, the gas replacing the varnish has a much lower dielectric strength. The base material may or may not deteriorate depending on whether it is organic or inorganic.
Keywords :
Dielectric breakdown; Dielectric liquids; Insulation; Power transformer insulation; Temperature distribution;
Journal_Title :
Electrical Engineering
DOI :
10.1109/EE.1949.6444752