• DocumentCode
    1498121
  • Title

    The influence of circuit parameters and contact materials on the reignition of high-frequency vacuum arcs

  • Author

    Lindmayer, Manfred ; Wilkening, Ernst-Dieter

  • Author_Institution
    Inst. fuer Elektrische Energieanlagen, Tech. Univ. Braunschweig, West Germany
  • Volume
    13
  • Issue
    1
  • fYear
    1990
  • fDate
    3/1/1990 12:00:00 AM
  • Firstpage
    69
  • Lastpage
    73
  • Abstract
    The extinction or reignition of high-frequency (HF) transients plays an important role in the generation of voltage surges. Investigations with currents of several hundred amperes peak and current frequencies from 100 kHz up to 1 MHz were made to examine the reignition behavior of short vacuum gaps using different contact materials. The experiments were carried out in an UHV test chamber connected to an L-C test circuit with voltages in the 10-kV range. Data on the statistical distribution of reignition voltages and their dependence on the parameters as well as on different TRV conditions are presented
  • Keywords
    circuit-breaking arcs; 10 kV; 100 to 1000 kHz; HF vacuum arc reignition; L-C test circuit; TRV conditions; UHV test chamber; contact materials; generation of voltage surges; influence of circuit parameters; reignition behavior; short vacuum gaps; statistical distribution of reignition voltages; voltages; Circuit breakers; Circuit testing; Coupling circuits; Dielectric materials; Equations; Frequency; Hafnium; Mutual coupling; Vacuum arcs; Voltage;
  • fLanguage
    English
  • Journal_Title
    Components, Hybrids, and Manufacturing Technology, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0148-6411
  • Type

    jour

  • DOI
    10.1109/33.52851
  • Filename
    52851