DocumentCode
1498121
Title
The influence of circuit parameters and contact materials on the reignition of high-frequency vacuum arcs
Author
Lindmayer, Manfred ; Wilkening, Ernst-Dieter
Author_Institution
Inst. fuer Elektrische Energieanlagen, Tech. Univ. Braunschweig, West Germany
Volume
13
Issue
1
fYear
1990
fDate
3/1/1990 12:00:00 AM
Firstpage
69
Lastpage
73
Abstract
The extinction or reignition of high-frequency (HF) transients plays an important role in the generation of voltage surges. Investigations with currents of several hundred amperes peak and current frequencies from 100 kHz up to 1 MHz were made to examine the reignition behavior of short vacuum gaps using different contact materials. The experiments were carried out in an UHV test chamber connected to an L -C test circuit with voltages in the 10-kV range. Data on the statistical distribution of reignition voltages and their dependence on the parameters as well as on different TRV conditions are presented
Keywords
circuit-breaking arcs; 10 kV; 100 to 1000 kHz; HF vacuum arc reignition; L-C test circuit; TRV conditions; UHV test chamber; contact materials; generation of voltage surges; influence of circuit parameters; reignition behavior; short vacuum gaps; statistical distribution of reignition voltages; voltages; Circuit breakers; Circuit testing; Coupling circuits; Dielectric materials; Equations; Frequency; Hafnium; Mutual coupling; Vacuum arcs; Voltage;
fLanguage
English
Journal_Title
Components, Hybrids, and Manufacturing Technology, IEEE Transactions on
Publisher
ieee
ISSN
0148-6411
Type
jour
DOI
10.1109/33.52851
Filename
52851
Link To Document