• DocumentCode
    1498296
  • Title

    Impact of Surface Roughness on Corona Discharge for 30-year Operating Conductors in 500-kV ac Power Transmission Line

  • Author

    Bian, Xingming ; Chen, Lan ; Yu, Deming ; Wang, Liming ; Guan, Zhicheng

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Shenzhen, China
  • Volume
    27
  • Issue
    3
  • fYear
    2012
  • fDate
    7/1/2012 12:00:00 AM
  • Firstpage
    1693
  • Lastpage
    1695
  • Abstract
    An investigation into the effect of surface roughness on corona discharge for a 30-year operating conductor in the first 500-kV transmission line in China is presented. Many substances were found to adhere to the conductor surface. Corrosion and deposits had rendered the operated conductor surfaces much rougher than those of the new one. The results show that surface roughness has a significant impact on corona discharge, and the corona inception voltage of the operated conductor would be reduced while the audible and radio noise would be increased.
  • Keywords
    conductors (electric); corona; power transmission lines; surface roughness; China; ac power transmission line; corona discharge; corona inception voltage; corrosion; operating conductors; surface roughness; time 30 year; voltage 500 kV; Conductors; Corona; Discharges; Rough surfaces; Surface discharges; Surface morphology; Surface roughness; Audible noise; conductor aging; corona cage; corona discharge; radio noise; surface roughness; ultraviolet;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2012.2190465
  • Filename
    6185711